Order code: | 8200R |
Guaranty time(months): | 24 |
|
Description:Conventional / Reflective type Beam smoke detector, detection range from 5 to 70m (100m with optional BEAM-LRK), surface mounting, one reflector 200mm x 230mm included, nominal supply voltage 12VDC or 24VDC, normal mode standby current max. 17mA, alarm current max. 39mA, reset voltage threshold min. 2.5V, reset time max. 0.3s, IP54, -30° to 55°C, four programmable fixed sensitivity levels 25%, 30%, 40%, 50% or two automatic variable sensitivity modes with sensitivy level from 30% to 50% or from 40% to 50%, automatic drift compensation and auto-adjusting, certificate 0832-CPD-0325 ( equivalent of 6500R )